Satec PM296 Uživatelský manuál

Procházejte online nebo si stáhněte Uživatelský manuál pro Zařízení Satec PM296. SATEC PM296 User Manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk

Shrnutí obsahu

Strany 1 - Installation and Operation

PM296/RPM096 Power Quality Analyzers Installation and Operation Manual

Strany 2

Chapter 1 Introduction 2Remote Display Module - Optional The RPM096 can be equipped with a Remote Display Module (RDM096) that provides local data

Strany 3 - LIMITED WARRANTY

Chapter 1 Introduction 3 Waveform Recorder for waveform capture and logging on different events. Along with the disturbance monitor it allows for cap

Strany 4

Chapter 1 Introduction 4 User-selectable options are provided (see Section 4.11): 1) Power calculation mode (P.cAL) 2) Energy rollover value Thi

Strany 5 - Table of Contents

Chapter 1 Introduction 5Measured Parameters NOTE: Real-time values are measured over 1 cycle of fundamental frequency; Average values are of 8, 16

Strany 6 - Quick Start

Chapter 1 Introduction 6 Outputs

Strany 7

Chapter 1 Introduction 7 Outputs Pa

Strany 8

Chapter 2 Installation 8 Chapter 2 Installation 2. 2.1 Mechanical Installation Figure 2-1 Front Mounting of the PM296

Strany 9 - 1.2 About The PM296/RPM096

Chapter 2 Installation 9 Figure 2-2 Mounting Brackets onto RPM096 Figure 2-3 RPM096 Mounting on DIN Rail

Strany 10

Chapter 2 Installation 10 Figure 2-4 Mounting the RDM096 on Square/Round Cutout Figure 2-5 Connection of RDM096 to RPM096

Strany 11

Chapter 2 Installation 11 2.2 Electrical Installation  Before installation ensure that all incoming power sources are shut OFF. Failure to observe

Strany 13 - Measured Parameters

Chapter 2 Installation 12 Wiring Configuration Wiring (See parameter setu

Strany 14 - Chapter 1 Introduction

Chapter 2 Installation 13 Figure 2-7 Four Wire WYE Direct Connection Using 3 CTs (3-element) Wiring Mode = 4LL3 or 4Ln3 Figure 2-8 Four Wire WYE

Strany 15

Chapter 2 Installation 14 Figure 2-9 Three Wire Open Delta Connection Using 2 PTs, 2 CTs (2-element) Wiring Mode = 3OP2 Figure 2-10 Four Wire Wye

Strany 16 - 2.1 Mechanical Installation

Chapter 2 Installation 15 Figure 2-11 Three Wire Open Delta Connection Using 2 PTs, 3 CTs (2½-element) Wiring Mode = 3OP3 Figure 2-12 Four Wire

Strany 17 - Chapter 2 Installation 9

Chapter 2 Installation 16 2.2.5 Relays Six relays are provided for energy pulsing, alarms or remote control. Figure 2-13 Relays Connection 2.2.6

Strany 18

Chapter 2 Installation 17 2.2.7 Analog Output The PM296/RPM096 provides two optically isolated analog outputs with an internal power supply and cur

Strany 19 - 2.2 Electrical Installation

Chapter 3 Using the Menus 18 Chapter 3 Using The Menus 3. Press and release to enter the setup mode. The primary menus will ap

Strany 20 - Wiring Mode = 3dir2

Chapter 3 Using the Menus 19 Figure 3-1 Menu Structure SELECTStAOPSCHGPASS bAScPortdinPCntAoutAEPnPulSt-rStatus InformationSetup

Strany 21

Chapter 4 Setup Menus 20 Chapter 4 Setup Menus 4. CHAPTER 3 SETUP MENUS NOTE: Instrument setup can be performed directly on the front panel usin

Strany 22

Chapter 4 Setup Menus 21 Table 4-1 Basic Setup Options (∗ default setting) Code Parameter Options Description Co

Strany 23

i LIMITED WARRANTY The manufacturer offers the customer an 24-month functional warranty on the instrument for faulty workmanship or parts from date

Strany 24 - 2.2.6 Status Inputs

Chapter 4 Setup Menus 22 Code Parameter Options Description rEc.C The number of cycles in a waveform series  0 to

Strany 25 - 2.2.8 DC Input

Chapter 4 Setup Menus 23 4.2 Communications Port Setup Menus These menus allow you to access the communications port opti

Strany 26 - Chapter 3 Using The Menus

Chapter 4 Setup Menus 24 Code Parameter Options Description dAtA Data format 7E 7 bits, even par

Strany 27

Chapter 4 Setup Menus 25 4.3 Digital Inputs Setup Menu This menu is used to set up the 12 digital inputs provided by the PM296/RPM096

Strany 28 - Chapter 4 Setup Menus

Chapter 4 Setup Menus 26 4.4 Pulse Counters Setup Menu This menu is used to configure the 16 pulse counters provided by your PM296/RP

Strany 29 - Chapter 4 Setup Menus 21

Chapter 4 Setup Menus 27 4.5 Analog Output Setup Menu [This section is relevant to instruments ordered with this option] This menu al

Strany 30

Chapter 4 Setup Menus 28 parameter. For signed (bi-directional) values, such as powers and signed power factor, the scale is always symmetrical wit

Strany 31

Chapter 4 Setup Menus 29 Code Parameter Unit Scale rt P Total kW kW/MW -

Strany 32

Chapter 4 Setup Menus 30 Wiring via PTs (PT Ratio > 1): Vmax (690 V input option) = 144 × PT Ratio [V] Vmax (120 V input option) = 144 × PT Rat

Strany 33

Chapter 4 Setup Menus 31 4.7 Pulsing Output Setup Menu This menu allows you to program either of the six relays provided by your PM296/RPM096 inst

Strany 34

iishorting switches and is secured using an external strain relief to reduce mechanical strain on the screw terminals, if necessary. 7. Setup proc

Strany 35 - 4.5 Analog Output Setup Menu

Chapter 4 Setup Menus 32 4.8 Timers Setup Menu This menu allows you to access the four interval timers provided by the PM296/RPM096 which can tri

Strany 36

Chapter 4 Setup Menus 33 4.9 RTC Setup Menu This menu allows you to view and set the time, date and day of week in the onboard Real Time Clock (RT

Strany 37

Chapter 4 Setup Menus 34 To select an option sub-menu:  From the upper window, use the up/down arrow keys to scroll to the desired sub-menu (time,

Strany 38

Chapter 4 Setup Menus 35 4.10 Display Setup Menu This menu allows you to view and change display properties. Table 4-6 lists available options wit

Strany 39

Chapter 4 Setup Menus 36 To select a display option:  Press to activate the middle window, and then use the up/down arrow keys to

Strany 40 - 4.8 Timers Setup Menu

Chapter 4 Setup Menus 37 Code Parameter Options Description An.Ou Analog output option (see Section 4.5) nonE∗ 0-20 4

Strany 41 - 4.9 RTC Setup Menu

Chapter 4 Setup Menus 38 4.12 Access Control Menu This menu can be only accessed via the Setup Change Menu (CHG). It is used in order to: • chang

Strany 42

Chapter 4 Setup Menus 39 4.13 Reset Menu This menu allows you to reset to zero the accumulators and Min/Max registers in your instrument. The menu

Strany 43 - 4.10 Display Setup Menu

Chapter 5 Data Display 40 Chapter 5 Data Display 5. 5.1 Navigating in the Display Mode The front panel has a simple interface that allows you to

Strany 44

Chapter 5 Data Display 41 The display is updated approximately twice per second; you can adjust the display update rate via the Display Setup Menu

Strany 45

iiiTable of Contents Quick Start ...iv Chapter 1 Introductio

Strany 46 - 4.12 Access Control Menu

Chapter 5 Data Display 42 Selecting Max Demand Measurements  In the RDM096, press the key. Use the up/down arrow keys to scroll

Strany 47 - 4.13 Reset Menu

Chapter 5 Data Display 43 Fast Reset of Accumulated Data  Select a display page where the data you want to reset is displayed. To reset: • M

Strany 48 - Chapter 5 Data Display

Chapter 5 Data Display 44 Page Window PAGE Parameter  Digits Unit  LEDs 1 9 Total k

Strany 49 - Selecting a Display Page

Chapter 5 Data Display 45 Page Window PAGE Parameter  Digits Unit  LEDs 7 3 Voltage

Strany 50

Chapter 5 Data Display 46 Page Window PAGE Parameter  Digits Unit  LEDs 2 4 Maximum

Strany 51 - ENTERSELECT

Chapter 5 Data Display 47 Page Window PAGE Parameter  Digits Unit  LEDs 20 8 Harmon

Strany 52

Chapter 5 Data Display 48 The RDM096 Data Display The display windows are labeled in the table as follows: 1 = upper window, 2 = middle window, 3 =

Strany 53

Chapter 5 Data Display 49 Page Window Arrow LED Parameter  Digits Unit  17 1 01H (Fundamental

Strany 54

Chapter 5 Data Display 50 Page Window Arrow LED Parameter  Digits Unit  8 1 A NEUT Maximum ne

Strany 55

Chapter 5 Data Display 51 Page Window Arrow LED Parameter  Digits Unit  1 3 MWh import 6 M

Strany 56

iv Quick Start TYPICAL INSTALLATION : Wiring Mode 4LL3, RS-485 Connection (see Sections 2.2.4 and 7.2 for complete set of diagrams) General Schemat

Strany 57

Chapter 5 Data Display 52 5.3 Self-Test Diagnostics Display The PM296/RPM096 periodically performs self-test diagnostics during operation. If the i

Strany 58

Chapter 6 Viewing Status Information 53 Chapter 6 Viewing Status Information 6. Through the Status Information Menu (STA), it is possible to view

Strany 59

Chapter 6 Viewing Status Information 54 6.2 Status Display Formats Tables 6-1 and 6-2 list all the displays available from the Status Information M

Strany 60

Chapter 6 Viewing Status Information 55 Page Window Parameter Digits

Strany 61 - Fast Reset of Counters

Chapter 7 Communications 56 Chapter 7 Communications 7. CHAPTER 6 USING A PRINTER A full description of the communications software is found in

Strany 62 - 6.2 Status Display Formats

Chapter 7 Communications 57 Table 7-1 Printout Record Parameters Line Place Heading Parameter 

Strany 63

Chapter 7 Communications 58 7.2 Connections Figure 7-1 RS-232 and RS-422/RS-485 Terminal Blocks RS-232 - up to 15 meters distance, 1 PC/PLC/Pri

Strany 64 - 7.1 Using a Printer

Chapter 7 Communications 59 Computer Connections for RS-232: COM1 Figure 7-8 RS-232 Simple 3-Wire Connection, 25-pin Figure 7-9 RS-232 Simple 3

Strany 65

Chapter 7 Communications 60 Computer Connections for RS-422: COM2 Computer Connections for RS-485: COM1 Figure 7-12 RS-422/RS-485 Connection

Strany 66 - 7.2 Connections

Chapter 7 Communications 61 Computer Multidrop Connections for RS-485: COM1 Figure 7-13 RS-485 Multidrop Connection, 25-Pin Connector Figure

Strany 67

v SETUP (see Chapter 4 for full instructions) Setups can be performed directly on the front panel or via PComTest/PAS communication software - see Ch

Strany 68

Chapter 7 Communications 62 Computer Multidrop Connections for RS-422/RS-485: COM2 Figure 7-15 RS-422 Multidrop Conne

Strany 69

Appendix: Technical Specifications 63 Appendix: Technical Specifications 8. ions Input and Output Ratings CATEGORY II POLLUTION DEGREE 2 (IEC

Strany 70

Appendix: Technical Specifications 64 Input and Output Ratings Current input terminal Rated 10A 250V Pitch 10 mm Wire 3 mm2 (10 AWG) Voltage inpu

Strany 71 - Input and Output Ratings

Appendix: Technical Specifications 65 Storage temperature -25°C to 80°C (-13°F to 176°F) Humidity 0 to 95% non-condensing Construction Instrume

Strany 72 - INSTALLATION CATEGORY II

Appendix: Technical Specifications 66 Measurement Specifications Parameter Full scale Accuracy, % Range Display resolution (%Rdg)  @ input Rd

Strany 73 - Standards Compliance

Appendix: Technical Specifications 67 Parameter Full scale Accuracy, % Range Display resolution (%Rdg)  @ input Rdg FS Conditions @ range c

Strany 74 - Measurement Specifications

Appendix: Technical Specifications 68 Parameter Full scale Accuracy, % Range Display resolution (%Rdg)  @ input Rdg FS Conditions @ range

Strany 75

Index 69 Index A accuracy, 32, 69 active energy, 67 active power, 36, 37, 66 ampere demand, v, 21, 31, 44, 49, 57 analog output, i, 2, 22, 27, 28, 3

Strany 77

Chapter 1 Introduction 1Chapter 1 Introduction 1. 1.1 About This Manual This manual is intended for the user of the PM296/RPM096 Power Quality Anal

Komentáře k této Příručce

Žádné komentáře